| Plan Review Notes For Permit 01010497 |
| Permit Number |
01010497 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-22 00:00:00 | ************* UNSAT ******************** | | | | | | 1)NOTE: PLEASE NOTE PER F.A.C PER | | | STATUE 553-79-6-A. PLANS SUBMITTED FOR | | | 480/277V NEED TO BE SIGNED AND SEALED BY | | | A PE. | | | | | | 2)NOTE: PLEASE SEE SHEET E-1 FOR COLOR | | | CODING OF FEEDERS. PLEASE SEE LOCAL | | | AMENDMENTS ART 215 | | | | | | 3)NOTE: PLEASE SEE 210-62 FOR SHOW | | | WINDOW OUTLETS. | | | | | | 4)NOTE: PLEASE SHOW CALCULATIONS FOR | | | TRACK LIGHTING PER 220-12B | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEW. | | | 561-659-8096 EXT 8372 |
|