| Plan Review Notes For Permit 01010497 |
| Permit Number |
01010497 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-22 00:00:00 | BUILDING PLAN REVIEW: | | | 1)- NOTE NOTICE OF COMENCEMENT IS GOOD | | | ONLY FOR 90 DAYS FROM DATE RECORDED IF | | | WORK HASN'T COMMENCED. | | | 2)- FL ENERGY CALCULATION WILL BE | | | REQUIRED AS PER FL. EN. CODE 400. | | | 3)- GLAZED OPENINGS WILL REQUIRE PROOF | | | OF LARGE MISSLE IMPACT TESTING,SBC | | | 1606.4.1/1707.4.1- THE CITY WILL PROVISO | | | THIS ISSUE, A SEPERATE SUB-PERMIT WILL | | | BE REQUIRED, A COPY OF THE CITIES POLICY | | | IS ENCLOSED AS WHAT WILL BE REQUIRED. | | | 4)- FL ACCESSIBILITY CODE 4.13.6- | | | MANEUVERING CLEARENCES AT DOORS AT HAND- | | | ICAPPED RESTROOM SEE FIGURE 25, A 24" | | | MINIMUM ON THE PUSH SIDE, SEE ATTACHMENT | | | 5)- SBC 803.3 PLEASE INDICATE THE INTER- | | | IOR MINIMUM FINISH CLASSIFICATION IN | | | ACCORDANCE WITH ASTM E-84. INDICATE THE | | | FLAMESPREAD & SMOKE DEVELOPMENT. | | | 6)- SBC 104.2.2-SHEET A-2 SEC A-A- | | | ADDITIONAL INFO. REQUIRED, A DROP CEIL- | | | ING OR SOFFITED CEILING NOTES: STUD | | | FRAMING SIZED TO MFGR? WHAT SIZE IS THE | | | FRAMING? HOW OFTEN IS THE TOP TRACK | | | FASTENED ABOVE, AND TO WHAT? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX. 8412 |
|