Plan Review Notes
Plan Review Notes For Permit 01010497
Permit Number 01010497
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-22 00:00:00BUILDING PLAN REVIEW:
 1)- NOTE NOTICE OF COMENCEMENT IS GOOD
 ONLY FOR 90 DAYS FROM DATE RECORDED IF
 WORK HASN'T COMMENCED.
 2)- FL ENERGY CALCULATION WILL BE
 REQUIRED AS PER FL. EN. CODE 400.
 3)- GLAZED OPENINGS WILL REQUIRE PROOF
 OF LARGE MISSLE IMPACT TESTING,SBC
 1606.4.1/1707.4.1- THE CITY WILL PROVISO
 THIS ISSUE, A SEPERATE SUB-PERMIT WILL
 BE REQUIRED, A COPY OF THE CITIES POLICY
 IS ENCLOSED AS WHAT WILL BE REQUIRED.
 4)- FL ACCESSIBILITY CODE 4.13.6-
 MANEUVERING CLEARENCES AT DOORS AT HAND-
 ICAPPED RESTROOM SEE FIGURE 25, A 24"
 MINIMUM ON THE PUSH SIDE, SEE ATTACHMENT
 5)- SBC 803.3 PLEASE INDICATE THE INTER-
 IOR MINIMUM FINISH CLASSIFICATION IN
 ACCORDANCE WITH ASTM E-84. INDICATE THE
 FLAMESPREAD & SMOKE DEVELOPMENT.
 6)- SBC 104.2.2-SHEET A-2 SEC A-A-
 ADDITIONAL INFO. REQUIRED, A DROP CEIL-
 ING OR SOFFITED CEILING NOTES: STUD
 FRAMING SIZED TO MFGR? WHAT SIZE IS THE
 FRAMING? HOW OFTEN IS THE TOP TRACK
 FASTENED ABOVE, AND TO WHAT?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX. 8412