| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-19 00:00:00 | 1) PLEASE INDICATE THE LOCATION AND | | | PROPOSED ROUTE, WHEN PERSONS EXIT FROM | | | DOORS 367. | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS. | | | 3) DOORS 307 AND 307 A MUST BE ABLE TO | | | SWING TIGHT AGAINST A WALL AS THEY | | | OPEN DIRECTLY OPPOSITE ONE ANOTHER. | | | 4) PLEASE PROVIDE COMPLETE FIRE ALARM | | | SYSTEM SHOP DRAWINGS FOR FIRE ALARM | | | EQUIPMENT SHOWN ON THE DRAWINGS. | | | SEPARATE PERMIT REQUIRED. | | | 5) FIRE SPRINKLER REMODEL TO BE DONE | | | UNDER SEPARATE PERMIT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|