| Plan Review Notes For Permit 01010487 |
| Permit Number |
01010487 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-13 00:00:00 | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION WITH MECHANICAL PERMIT | | | APPLICATION: | | | | | | O.A. CALCULATIONS AS PER ASHRAE 62-89. | | | | | | KEY NOTES ON DRAWING A-4 #19 & 20, | | | EXHAUSET SHALL BE 10' FROM OR 24" ABOVE | | | O.A. INTAKE.ONE OF THE EXHAUST OULETS | | | WHEN SCALED ON PLAN IS ONLY 4' 6" FROM | | | O.A. INTAKE. | | | | | | SUBMIT DETAIL ON CONDENSER UNIT STANDS. | | | | | | AHU'S WITH FAN CAPACITY GREATER THAN | | | 2,00 CFM SHALL HAVE FAN SHUTDOWN BY | | | DUCT SMOKE DETECTOR AS PER 1997 SMC | | | 406.1 AND HAVE NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | | | | | PLEASE INDICATE ON PLAN WHERE THE | | | CONDENSATE IS BEING DISPOSED. |
|