| 2001-01-26 00:00:00 | DENIED; | | | | | | 1.COFFEE ROOM SINKS SHALL COMPLY WITH | | | FACBC 4.24.1 THRU 4.24.7. | | | | | | 2.DRINKING FOUNTAIN SHALL COMPLY WITH | | | FACBC 4.1.3 (10) AND 4.15. PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING OR STOOPING. CHECK | | | CLEAR FLOOR SPACE, SECOND FLOOR | | | DRINKING FOUNTAIN 30"X 48". | | | | | | 3.P-3 (RISER DIAGRAM) HORIZONTAL DRY | | | VENTS ARE NOT PERMITED. 94 SPC 914.2. | | | | | | 4.WATER RISER DIAGRAM REQUIRED. | | | | | | 5.PROVIDE RAIN FALL CALCULATIONS, TOTAL | | | SQUIRE FOOTAGE OF ROOF AREA FOR EACH | | | ROOF DRAIN AND DEGREE OF PITCH FOR | | | HORIZONTAL RAIN LEADERS AND STORM | | | SEWER. SPC TABLE 1108.1, 1108.2 AND | | | 1108.4. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|