| Plan Review Notes For Permit 01010487 |
| Permit Number |
01010487 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-05 00:00:00 | *************DENIED********************* | | | 1. VENT STACKES AND EXHAUST OUTLETS | | | SHALL BE MINIMUM 10 FOOT FROM OUTSIDE | | | AIR INTAKE PER 1997 SMC 405SEE A-3 | | | 2. OUTSIDE AIR SCHEDULE AND A/C | | | EQUIPMENT SCHEDULES DO NOT MATCH. | | | PROVIDE CORRECTED INFORMATION ON | | | OUTSIDE AIR TO MATCH EQUIPMENT SUPPLIED. | | | 3. PROVIDE FIRE DAMPER INSTALLATION | | | INFORMATION PER 1997 SMC 610. | | | 4. EXHAUST FANS FROM RR103 AND RR 103A | | | DUCT THROUGH WALL AND UP THROUGH 2ND | | | FLOOR. DUCTS FROM 1ST FLOOR NEED TO BE | | | ENCLOSED IN SHAFT THROUGH 2ND FLOOR PER | | | 1997 SMC 610.4. | | | 5. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 |
|