| Date |
Text |
| 2001-01-17 00:00:00 | 1) ELEVATION DRAWINGS DID NOT DISPLAY |
| | BUILDING ADDRESS. BUILDING ADDRESS TO |
| | BE INSTALLED AND COMPLY WITH CITY CODE |
| | REQUIREMENTS. |
| | 2) AWNINGS PLANNED FOR USE ARE TO BE |
| | FIRE RETARDANT. |
| | 3) IT APPEARS THAT ANOTHER FIRE HYDRANT |
| | IS NEEDED NEAR THE BUILDING. THE FIRE |
| | SPRINKLER SYSTEM CONNECTION FOR THE |
| | BUILDING SHALL NOT EXCEED 150 FEET FROM |
| | A FIRE HYDRANT. |
| | 4) PLEASE INDICATE WHAT THE FUTURE RAMP |
| | AND PLATFORM WILL BE USED FOR. ARE THESE |
| | WHEN INSTALLED, TEMPORARY OR PERMANANT. |
| | WHAT CONSTRUCTION TYPE WILL THEY BE. |
| | 5) ELEVATOR TO COMPLY WITH ANSI A17.1 |
| | 6) PORTABLE FIRE EXTINGUISHERS WHEN |
| | INSTALLED, ARE TO BE EQUIPPED WITH A |
| | CURRENT SERVICE TAG. |
| | 7) PLEASE PROVIDE COMPLETE FIRE |
| | SPRINKLER SYSTEM DRAWINGS AND HYDRAULIC |
| | CALCULATIONS TO THIS OFFICE. SEPARATE |
| | PERMIT REQUIRED. |
| | 8) PLEASE PROVIDE COMPLETE FIRE ALARM |
| | SYSTEM DRAWINGS TO THIS OFFICE. CUT |
| | SHEETS, WIRING DIAGRAM, BATTERY |
| | CALCULATIONS, FLOOR PLANS ARE REQUIRED. |
| | 9) THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM TO BE SUPERVISED BY A |
| | LICENSED UL LISTED CENTRAL STATION |
| | APPROVED BY THE FIRE RESCUE DEPARTMENT. |
| | 10) A KNOX-BOX WILL BE REQUIRED FOR |
| | RAPID FIRE ACCESS. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |