| Date |
Text |
| 2001-01-30 00:00:00 | DENIED; |
| | |
| | 1.HANDICAP RESIDENCE UNIT A-8 "TYPICAL |
| | ROOM PLAN", DOOR SWINGS INTO CLEAR |
| | FLOOR SPACE OF LAV. FACBC 4.19.3. |
| | |
| | 2.HORIZONTAL RAIN WATER LEADERS AT 1/8" |
| | PITCH PER. FT. CAN CARRY 5350 SQ. FT. |
| | NOT 5400 SQ. FT.INCREASE PITCH OR PIPE |
| | SIZE. |
| | |
| | 3.GAS PIPING. SUBMIT THE FOLLOWING |
| | INFORMATION; LONGEST RUN IN FEET,TYPE |
| | OF PIPE TO BE USED, AND SPECIFCATION |
| | SHEETS FOR REGULATOR. |
| | |
| | 4.FLOOR DRAIN IN LAUNDRY ROOMS SHALL BE |
| | DEEP SEAL TRAPS OR EQUIPED WITH TRAP |
| | PRIMERS. |
| | |
| | 5.DRINKING FOUNTAIN TO COMPLY WITH FACBC |
| | 4.1.3(10) AND 4.15. PROVISIONS SHALL |
| | BE MADE FOR PEOPLE WHO HAVE TROUBLE |
| | BENDING OR STOOPING. |
| | |
| | 6.EWH-1 RELIEF VALVE SHALL BE PIPED TO |
| | THE OUTSIDE. 94 SPC 507.8.4. |
| | |
| | 7.EWH-2 SHEET A-7 NOTE 8 IS NOT SHOWN ON |
| | WATER RISER OR FLOOR PLAN. |
| | |
| | 8.ATMOSPHERIC VACUUM BREAKER REQUIRED ON |
| | GAS WATER HEATERS, WHERE COLD WATER |
| | ENTERS THE BOTTOM 1/2 OF THE HEATER. |
| | |
| | 9.APPROVED MECHANICAL AIR CHAMBERS TO BE |
| | USED SPC 607.8.2 AND MUST BE |
| | ACCESSIBLE 607.8.3. |
| | |
| | 10.PAGE A-17A GAS RISER DIAGRAM NOTE |
| | STATES 3 WATER HEATER LOCATIONS. |
| | WHERE IS THIRD GAS WATER HEATER? |
| | |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 659-8096 EXT. 8377 |