| Plan Review Notes For Permit 01010486 |
| Permit Number |
01010486 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-05 00:00:00 | ***************DENIED******************* | | | 1.FIRE DAMPERS ARE NOT SHOWN AT THE | | | WALL PENETRATION BETWEEN THE STORAGE | | | ROOMS AND THE CORRIDORS WHERE THE | | | TRANSFER DUCT AND THE SUPPLY AIR DUCT | | | PENETRATE THE WALLS. SHOW LOCATION AND | | | INSTALLATION DETAILS PER 1997 SMC 610.6. | | | 2. OUTSIDE AIR SCHEDULE DOES NOT | | | CORRESPOND TO THE ROOF TOP EQUIPMENT | | | NUMBERS INDICATED IN THE EQUIPMENT | | | SCHEDULE NUMBERS. CORRECT NOTES TO | | | REFLECT EQUIPMENT PROVIDED. | | | 3. THERE ARE TWO RTU 7 INDICATED ON | | | A-18AND NO RTU- 6 ON THE A/C PLAN. | | | INDICATE CORRECT UNIT NUMBERS ON PLAN. | | | 4. WILL THERE BE PERSONNELL ACCESS TO | | | THE HIGH ROOF OVER THE PARAPET WALL? | | | 5. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | NOT SHOWN ON PLAN. ANY EQUIPMENT SERVING | | | AREAS USED FOR EGRESS SHALL HAVE FAN | | | SHUT DOWN BY DUCT SMOKE DETECTOR WITH | | | NOTIFICATION BY BUILDING FIRE ALARM | | | SYSTEM PER 1997 SMC 406.2 AND NFPA 96 | | | 4-4.4 |
|