| Plan Review Notes For Permit 01010454 |
| Permit Number |
01010454 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-24 00:00:00 | BUILDING PLAN REVIEW | | | VERTICAL PLATFORM LIFT | | | 1). FL. ACCESSIBILTY CODE 4.11: PLATFORM | | | & WHEELCHAIR LIFTS REQUIRE APPROVAL FROM | | | ASME A 17.1. | | | 2). SBC 1606.2.6.2 COMPONENTS & CLADDING | | | DOES THIS UNIT HAVE TESTING FOR A 110 | | | MPH WIND AREA? | | | 3). FL. ACC. CODE 4.27 CONTROLS AND | | | OPERATING MECHANISMS: HEIGHT OF CONTROL | | | CALL BOX? | | | 4). FL. ACC. CODE 4.27.4 CONTROLS AND | | | OPERATING MECHANISMS SHALL BE OPERATABLE | | | WITH ONE HAND & SHALL NOT TIGHT GRASPING | | | PINCHING, OR TWISTING OF THE WRIST. THE | | | FORCE REQUIRED TO ACTIVATE THE CONTROLS | | | SHALL BE NO GREATER THAN 5 LBF. | | | 5). SBC 104.2.2 ADITIONAL INFO: PLANS | | | INDICATE A ENCLOSURE (DOOR) ON THE LIFT. | | | WHEN THE LIFT IS AT LANDING #1, WHAT IS | | | THE PROTECTION ON LANDING #2 THAT KEEPS | | | SOMEONE FROM FALLING INTO THE SHAFT? IS | | | THERE A GATE AT LEVEL # 2 THAT DOES THIS | | | AND IS THER A INTER LOCK THAT IF GATES | | | ARE OPEN THE UNIT WILL NOTACTIVATE? | | | WHAT SIZE ARE THE LAGS TO BE USED? THE | | | TOWER OR MAST IS MADE OF WHAT MATERIAL & | | | WHAT IS THE MINIMUM SIZE REQUIRED? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX.8412 |
|