| Notes |
| Date |
Text |
| 2001-01-18 00:00:00 | 1) UNDERGROUND FIRE LINE INSTALLATION | | | TO COMPLY WITH NFPA 24. | | | 2) ENTIRE BUILDING TO BE COMPLETELY FIRE | | | SPRINKLER PROTECTED. THIS INCLUDES ALL | | | MECHANICAL, ELECTRICAL AND SERVICE ROOMS | | | ALSO ALL VERTICAL SHAFTS ARE TO BE | | | FIRE SPRINKLER PROTECTED. | | | 3) THE FIRE DEPARTMENT CONNECTION SHOWN | | | ON SITE PLAN IS POSITIONED THAT HOSE MAY | | | KINK WHEN IT IS CONNECTED. PLEASE | | | ADJUST AS NECESSARY. | | | 4) PLEASE PROVIDE SPARE HEAD BOX AND | | | WRENCH. | | | 5) UNDERGROUND PIPING AND FIRE SPRINKLER | | | SYSTEM TO BE PRESSURE TESTED AT 200 PSI. | | | FOR TWO HOURS. | | | 6) FIRE HYDRANT INSTALLATION TO COMPLY | | | WITH CITY REQUIREMENTS. | | | 7) NO CUT SHEETS PROVIDED FOR FIRE | | | SPRINKLER HEADS PLANNED FOR USE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|