| Plan Review Notes For Permit 01010407 |
| Permit Number |
01010407 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-16 00:00:00 | ****************** UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE CORRELATE WIRE SIZE TO | | | OCP. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM, PLANS | | | ARE SHOWING NEW METER/MAIN COMBO? IF | | | THIS THE CASE, PLEASE SUBMIT AIC RATING | | | OF NEW EQUIPMENT. | | | | | | 3)NOTE: PLEASE PROVIDE LAYOUT FOR | | | CONDUIT SIZING. | | | | | | PLEASE PROVIDE THE ABOVE INFORMATION | | | FOR REVIEW.F THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|