Plan Review Notes
Plan Review Notes For Permit 01010407
Permit Number 01010407
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-16 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE CORRELATE WIRE SIZE TO
 OCP.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, PLANS
 ARE SHOWING NEW METER/MAIN COMBO? IF
 THIS THE CASE, PLEASE SUBMIT AIC RATING
 OF NEW EQUIPMENT.
  
 3)NOTE: PLEASE PROVIDE LAYOUT FOR
 CONDUIT SIZING.
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 FOR REVIEW.F THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372