2001-01-10 00:00:001) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL AND SERVICE
 ROOMS. ANY VERTICAL SHAFTS ARE ALSO TO
 BE FIRE SPRINKLER PROTECTED.
 2) FIRE SPRINKLER SYSTEM TO BE INSTALLED
 IN ACCORDANCE WITH NFPA 13.
 3) SPARE HEAD BOX AND WRENCH REQUIRED.
 4) FIRE HYDRANTS TO COMPLY WITH CITY
 UTILITY AND FIRE RESCUE REQUIREMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497