| 2001-02-15 00:00:00 | PERMIT # 01010147 |
| | 201 CLEMATIS ST |
| | DAVID BROOKS ENTERPRISES |
| | PHONE: 863-1200 |
| | |
| | STRUCTURAL PLAN REVIEW: |
| | THE ISSUES THAT WERE IN CONFLICT WITH |
| | THE CODE HAVE ALL BEEN ADDRESSED ACCEPT |
| | FOR THE FIRST ISSUE, THE OCCUPANT LOAD. |
| | AS A RULE OF THUMB WHEN THERE IS A |
| | DIFFERENCE IN CODE INTERPRETATION, |
| | WE TAKE THE ISSUE TO THE BUILDING |
| | OFFICIAL FOR A FINAL INTERPRETATION.THE |
| | BUILDING OFFICIAL AGREES THAT THE |
| | OCCUPANT LOAD FOR THE 991 SQ. FT. @ 15FT |
| | PER PERSON YIELDS AN OCCUPANT LOAD OF |
| | 66 PEOPLE. |
| | 1)- SBC 1004.1.2: EVERY ROOM OR TENANT |
| | SPACE WHICH HAS AN OCCUPANT LOAD OF 50 |
| | OR MORE PERSONS SHALL NOT HAVE LESS THAN |
| | (2) TWO EGRESS DOORS. |
| | 2)-SBC 1004.1.4: WHERE TWO OR MORE EXITS |
| | OR EXIT ACCESS DOORS ARE REQUIRED, AT |
| | LEAST TWO OF THE EXIT DOORS OR EXIT |
| | ACCESS DOORS SHALL BE PLACED A DISTANCE |
| | APART EQUAL TO NOT LESS THAN ONE HALF |
| | OF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED MEASURED IN A STRAIGHT |
| | LINE BETWEEN SUCH EXITS OR EXIT ACCESS |
| | DOORS. |
| | |
| | THE SECOND ISSUE THAT THE BUILDING |
| | OFFICIAL BROUGHT UP IS FLOOR LOADING. |
| | WHEN THIS BUILDING WAS C.O.,EDTHIS |
| | AREA WAS TO BE USED FOR LIGHT STORAGE OF |
| | PROPS. THERE IS A NEED TO DO A FLOOR |
| | ANALYSIS TO SEE IF THE EXISTING FLOOR |
| | JOIST WILL MEET THE FLOOR LOADING OF |
| | 100 PSF LIVE LOAD AS PER SBC TABLE |
| | 1604.1 FOR THEATERS: AISLES, CORRIDORS |
| | AND LOBBIES. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX.8412 |