Plan Review Notes
Plan Review Notes For Permit 01010147
Permit Number 01010147
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-22 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 ELEC REQ`D FOR BAR/KITCHEN EQUIPMENT
 SHOWN ON E-201. ALL BRANCH CIRCUIT #`S
 ARE TO BE SHOWN. #`S ARE SHOWN BUT NOT
 PANELS? PLEASE SHOW THE PANEL SCHEDULE
 FOR THESE ITEMS. E-201 IS NOT SHOWN AS
 PHASE II.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 3)NOTE: PLEASE SEE REVISED LOAD SUMMARY
 SHOWN ON UPPER LEFT SIDE OF SHEETE-301
 NOTED AS PHASE II. PLEASE NOTE THE ADDED
 AMPERAGES. 17,466 AMPS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372