| 2001-01-18 00:00:00 | 1). OCCUPANT LOAD & MEANS OF EGRESS- |
| | SBC TABLE 1003.1 WITH 991 SQ. FT. TABLE |
| | 1003.1 SETS THE OCCUPANT LOAD AS 66 |
| | PEOPLE.SECTION 1020.1.3 STATES FOR A |
| | BUSINESS OCCUPANCY ABOVE THE GROUND |
| | FLOOR NO MORE THAN 40 PEOPLE ABOVE THE |
| | STREET WITH A SINGLE EXIT. |
| | 2).SBC 104.2.2- ADDITIONAL INFORMATION |
| | WILL BE REQUIRED: |
| | A). A FIRE SPRINKLER PLAN WILL BE RE- |
| | QUIRED. |
| | B). THE PLANS AREN'T CLEAR WITH WHAT |
| | LOOKS LIKE IT COULD BE A CHAIR LIFT |
| | IF IT IS WE NEED CUT SHEETS, SHAFT |
| | RATING, OPENING PROTTECTIVES FOR |
| | THE SECOND FLOOR.IF NOT, FL. ACC- |
| | ESSIBILITY CODE REQUIRES VERTICAL |
| | ACCESSIBILITY FOR CHANGES IN |
| | ELEVATION (FL ACC 4.3.8.C), THIS |
| | ALSO INCLUDES THE CHANGE IN HEIGTH |
| | AT THE ENTRY DOOR AS WELL AS AT THE |
| | ELEVATED BAANQUET SEATS 7". |
| | 3). PLANS INDICATE THIS IS A FIRE |
| | SPRINKLERED BUILDING, PLEASE INDICATE |
| | (TABLE 803.3) THE MINIMUM INTERIOR FIN- |
| | ISH CLASSIFICATIONS. |
| | 4).PLANS INDICATE GLAZING NEXT TO THE |
| | ENTRY DOOR(SBC 2405.2.3) REQUIRES THAT |
| | SAFETY GLAZING BE INSTALLED,HAZARDOUS |
| | LOCATION. |
| | 5).FL. ACC. CODE 4.13.9 DOOR HARDWARE- |
| | HANDLES,PULLS,LATCHES,LOCKS, AND OTHER |
| | OPERATING DEVISES ON ACCESSIBLE DOORS |
| | SHALL HAVE A SHAPE THAT IS EASY TO GRASP |
| | LEVER-OPERATED MECANISMS, PUSH-TYPE |
| | MECHANISMS AND U-SHAPED HANDLES ARE |
| | ACCEPTABLE DESIGNS. |
| | |