Plan Review Notes
Plan Review Notes For Permit 01010142
Permit Number 01010142
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. SOFFITS PLANNED ARE NOT TO
 INTERFERE WITH FIRE SPRINKLER HEAD
 DISCHARGE PATTERNS.
 2) PLEASE PROVIDE MORE DETAILS ON
 RECESSED VOLKSWAGON PLANNED FOR THE
 INTERIOR.
 3) ENTRY DOORS TO SWING IN THE DIRECTION
 OF EXIT TRAVEL. THE SALES FLOOR AREA OF
 2,636 SQUARE FEET DIVIDED BY 30 SQUARE
 FEET PER PERSON PROVIDES FOR AN OCCUPANT
 LOAD OF 87 PERSONS. DOORS MUST SWING
 IN THE DIRECTION OF EXIT TRAVEL.
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS.
 5) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST,
 DOOR LEADING TO STOCKROOM IS NOT SUBJECT
 TO LOCKING, AN AISLE OF AT LEAST 44
 INCHES WIDE IS PROVIDED AND MAINTAINED,
 AND ONLY 50 PERCENT OF EXIT ACCESS IS
 PROVIDED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910