| 2001-01-19 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | | | | 2)NOTE: PLEASE SUBMIT CLARIFICATION FOR | | | EQUIPMENT GROUNDING BETWEEN MAIN | | | DISCONNECT AND PANEL "B" AND PANEL"B" | | | TO PANEL"A". | | | | | | 3)NOTE: PLEASE SUBMIT CLARIFICATION ON | | | TRACK LIGHTING LOADS. PLEASE SHOW PER | | | 220-12B. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|