| Plan Review Notes For Permit 01010092 |
| Permit Number |
01010092 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-06 00:00:00 | 1) FIRE ALARM SYSTEM TO BE CLASS A OR | | | ADDRESSABLE. | | | 2) SMOKE DETECTOR REQUIRED ABOVE FIRE | | | ALARM CONTROL PANEL. | | | 3) FIRE SPRINKLER SYSTEM AND ALARM | | | SYSTEM TO BE SUPERVISED BY A LICENSED | | | UL LISTED CENTRAL STATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|