| 2001-01-17 00:00:00 | BILDING PLAN REVIEW: | | | 1). SBC 104.2.2- DOOR SCHEDULE IS MISS- | | | ING INFORMATION FOR DOOR #3. | | | 2). NOTE DOOR #3, IF USED IN A EXIT | | | ACCESS THE NET CLEAR OPENING CAN NOT BE | | | LESS THAN 32". | | | 3). FL. ACCESSIBILITY CODE 4.13.5- | | | CLEAR WIDTH OF DOORS, THE DOORS LEADING | | | INTO THE HANDICAPPED RESTROOMS WILL | | | REQUIRE A CLEAR 32" OPENING, MEASURING | | | FROM THE FACE OF THE DOOR TO THE DOOR | | | STOP ON THE OTHER JAMB. | | | 4). FL. ACCESIBILITY CODE 4.13.6- | | | MANEUVERING CLEARENCES AT DOORS- SEE | | | RESTROOM DOORS INTERIOR LATCH SIDE | | | REQUIRES 18" MINIMUM. | | | 5). SEE FL. ACCESSIBILITY FOR DISPRO- | | | PORTIONATE COST 20%. SEE ATTACHMENT. | | | 6). SBC 704.3 OFFICE #119 WILL REQUIRE | | | A 1 HR WALL FOR TENANT FIRE SEPERATION. | | | WILL NEED A DETAIL FOR THE WALL FROM | | | FLOOR TO CEILING, UL LISTING OR GYPSUM | | | NUMBER. | | | 7). ENERGY CALS SIGNED BY THE PERSON PRE | | | PARING THE COMPLIANCE CALULATION. | | | | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | (561) 659- 8096 EX 8412 |
|