| Plan Review Notes For Permit 01010057 |
| Permit Number |
01010057 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT THE BUILDING. | | | 3) FIRE ALARM SYSTEM TO BE CLASS A OR | | | FULLY ADDRESSABLE. | | | 4) FIRE ALARM SYSTEM TO BE MONITORED BY | | | A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|