| Plan Review Notes For Permit 01010048 |
| Permit Number |
01010048 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-06-27 00:00:00 | PLUMBING PLAN REVIEW 3RD TIME DENIED | | | SEE ATTACHED (PREVIOUS PLAN REVIEWS) | | | (1) NUMBER SHEETS FOR REFERENCE, 104.3 | | | (2) MINIMUM SIZE OF GREASE TRAP 750 GAL | | | CONTACT WPB REGIONAL SEWER TREATMENT | | | PLANT, SIZE. RODNEY COMPO 561-8374074 | | | (3) SPC 94 SEC 104.3 PLANS, SPECIFICA- | | | TIONS, PROVIDE A ISOMETRIC DRAWING OF | | | DWV,WATER PIPING, SHOW LOCATION OF BACK | | | FLOW PREVENTER ON WATER SERVICE, FUTURE | | | CONNECTION FOR CAR WASH, ALL INDIRECT | | | WASTE TO FLR SINKS, ICE MACHINE AND | | | COOLER. FUTURE SANI SEWER FOR CAR WASH. | | | (4) SEE ATTACHED: GAS PERMIT APPLICATION | | | REQUIRMENTS ADDRESS EA ITEM CIRCLED. | | | (5) SEPERATE PRRMITS FOR GAS, IRRIGATION | | | GREASE INTERCEPTOR. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|