| 2001-07-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01010048 |
| | 1300 N TAMARIND AV |
| | CONT: FLORIDA GENERAL CONT. |
| | PHONE : 722-5454 |
| | |
| | THE RENDERING OF THE CANOPY DOES NOT |
| | HAVE SUFFICIENT STUCTURAL INFORMATION TO |
| | BE ABLE TO DO A COMPENTENT STRUCTURAL |
| | PLAN REVIEW AT THIS TIME. |
| | |
| | 1)- A STUCTURAL DESIGN CERTIFICATION |
| | CODE ANALYSIS NEEDS TO BE COMPLETED FOR |
| | THE CANOPY. ATTACHED COPY. |
| | |
| | 2)- MISSING IS THE ENGINEERS' ANALYSIS |
| | FOR MOMENT OF OVERTURNING FOR THE CANOPY |
| | |
| | 3)- MISSNG IS THE FOOTING AND MONOLITHIC |
| | PAD INFORMATION, GRADE OF STEEL, SPACING |
| | SIZE OF STEEL,PLACEMENTAND INFORMATION |
| | ON THE CONCRETE MIX. |
| | |
| | 4)- ENGINEER TO GIVE THE P.S.F. THAT |
| | WILL BE REQUIRED FOR THE (3) FOOTINGS OF |
| | THE CANOPY. |
| | |
| | 5)- SOILS REPORT FOR THE CANOPY. |
| | |
| | 6)- TUBULAR COLUMNS: MISSING IS THE SIZE |
| | OF THE STEEL,GRADE, THICKNESS OF THE |
| | WALL,LBS/FT CONNECTIONS AT THE FOOTER |
| | AND TO THE CANOPY FRAME, WELDS/ TYPE. |
| | |
| | 7)- CANOPY FRAMING: NO INFORMATION IS |
| | GIVEN: SBC 404.2.2. REQUIRES THE CANOPY |
| | AND SUPPORTS TO BE 1HR. OR TYPE III |
| | CONSTRUCTION. |
| | |
| | 8)- NO INFORMATION IS GIVEN AS TO THE |
| | FINISH MATERIALS,SIDES, ROOF DECKING, |
| | GUTTERS & LITTERS OR SIGNAGE. |
| | |
| | 9)- SBC 404.2.2(2) THE CANOPY MUST MEET |
| | THESE REQUIREMENTS. |
| | |
| | 10)- SBC 404.2.4. PUMPS INSTALLED ABOVE |
| | GRADE SHALL BE MOUNTED ON A CONCRETE |
| | FOUNDATION & PROTECTED AGAINST VEHICLE |
| | DAMAGE. |
| | EXISTING BUILDING: |
| | 11)- CANOPY "A" THE DRAWINGS INDICATE |
| | THE CANOPY TO BE MADE OUT OF 2X4 TRUSSES |
| | THEY ALSO INDICATE THAT THERE WILL BE A |
| | DOUBLE 2X4 BOLTED TO THE WALL. THE |
| | PROBLEM IS WITH THE 9" TAP-CONS WE CAN |
| | NOT FIND IN ANY CATALOGS 9" TAP-CONS, |
| | PLEASE SUBMIT THE MANUFACTURES SPECS. |
| | |
| | 12)- RESTROOM: SBC 1203.4.2/SMC 503.3.2 |
| | REQUIRES COMMERCIAL RESTROOMS TO HAVE A |
| | MINIMUM 2 CU.FT./ MIN EXCHANGE OF AIR |
| | WHERE THERE IS NO WINDOW. |
| | |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |