| Plan Review Notes For Permit 01010048 |
| Permit Number |
01010048 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-04-30 00:00:00 | REVIEW NOTES:FACBC-97SPC-94 | | | | | | DENIED: | | | | | | (1) BATHROOM SIZE NOT SUFFICIENT. DOES | | | NOT COMPLY WITH FACBC-97 4.16 AND 4.19 | | | | | | (2) HEALTH DEPT. REVIEW AND APPROVAL | | | NOT SEEN. | | | | | | (3) FLOOR DRAIN NOT SEEN ON SANITARY | | | RISER DIAGRAM. | | | | | | (4) GREASY WASTE RISER DIAGRAM NOT | | | SUBMITTED. | | | | | | (5) NO CAR WASH DETAILS GIVEN. | | | | | | (6) LOCATION OF COOLER CONDENSATE | | | DISPOSAL NOT SHOWN. | | | | | | (7) FLOOR SINK REQUIRED FOR ICE MACHINE | | | DRAINS. | | | | | | (8) FLOOR SINK REQUIRED FOR INDIRECT | | | WASTE AT 3 COMPARTMENT SINK. SPC 807 | | | | | | (9) SUBMIT COPY OF REPORT FORM RODNEY | | | COMPO ON LOCATION AND SIZE OF GREASE | | | TRAP. |
|