Plan Review Notes For Permit 01010048
Permit Number 01010048
Review Stop B
Sequence Number 2
Notes
Date Text
2001-04-23 00:00:00THE PLANS DO NOT COMPLY WITH THE
 RESPONSIBILITY RULES OF PROFESSIONAL
 ENGINEERS CONCERNING THE DESIGN OF
 STRUCTURES AS FOUND IN CHAPTER 61G15-31
 OF THE FLORIDA ADMINISTRATIVE CODE.
 THE CANOPY, FOUNDATIONS AND GAS PUMPS
 HAVEFAR TOO FEW DETAILS
 DIMENSIONS OR SIZES.THERE IS NO
 DELEGATION OF DESIGN TO A SPECIALTY
 ENGINEER.THERE ARE NO CONNECTION
 DETAILS.
  
 THE FRAMING DETAIL FOR THE EXTERIOR
 MANSARD TYPE ROOF IS NOT CLEAR.
  
 PROVIDE
 MORE DETAIL AND THE DESIGN STANDARDS
 USED FOR THE DESIGN OF THE GASOLINE
 PUMPS AND THEIR PIPING.
  
 ASPHALT SHINGLES CANNOT BE USED ON A
 1:12 PITCH ROOF.