| Date |
Text |
| 2001-01-31 00:00:00 | *************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT UNDER F.A.C. |
| | SECTIONS 61G15-23.002 AND 471.025 ALL |
| | PLANS ARE TO CONTAIN TITLE BLOCK WITH |
| | ALL INFORMATION FOR ENGINEER OF RECORD. |
| | |
| | 2)NOTE: PLEASE NOTE THAT PLANS ARE |
| | SHOWING,,,," ELECTRICAL REQUIREMENSTS |
| | OPTIONAL."?? PLEASE CLARIFY THIS. |
| | PLEASE NOTE |
| | RISER/PANEL SCHEDULE NOTES,,,ALL WORK |
| | TOCOMPLY WITH "MEC" TYPE-O |
| | |
| | 3)NOTE: PLEASE SEE RISER, SHOWING 125A |
| | DISCONNECT AND 240A PANEL? |
| | |
| | |
| | 4)NOTE: ALSO IN NOTES, PANEL RATED |
| | 10,000 W. W- WATTS? PLEASE CLARIFY. |
| | |
| | 5)NOTE: PLEASE SHOW ALL ELECTRICAL |
| | OUTLET REQ`MENTS ON PLANS AND SHOW ALL |
| | BRANCH CIRCUIT #`S ON PLANS AND |
| | CORRELATE WITHPANEL SCHEDULES.215-5 |
| | |
| | 6)NOTE: NEED TO SHOW MORE DETAIL ON |
| | CLASS LOCATIONS/WIRING METHODS OF GAS |
| | PUMPS ETC. SEE ARTS IN ART 500 |
| | |
| | 7) NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) |
| | |
| | 8)NOTE: SUBMIT LOAD CALCULATIONS. 215-5 |
| | |
| | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 10)PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. NEED TO SHOWA/C |
| | EQUIPMENT ON PLANS. |
| | |
| | 11)PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | |
| | 12)NOTE: PLEASE SHOW CONDUCTORS BETWEEN |
| | MAIN AND PANEL. 215-5 |
| | |
| | 13)NOTE: PLEASE SEE PANEL SCHEDULES AND |
| | EXPLAIN " LIVING ROOM, DINING RM, |
| | BEDROOMS 1,2,3??????? |
| | |
| | 14)NOTE: PLEASE EXPLAIN #16 AWG ON PANEL |
| | SCH???? |
| | |
| | 15)NOTE: RAISED SEALED IS TO BE |
| | COMPLETELY VISIBLE. |
| | |
| | 16)NOTE: ALL EQUIPMENT TO BE SHOWN ON |
| | PANEL SCHEDULES AND LOAD CALCULATIONS. |
| | |
| | 17)NOTE: SHOW CONDUCTOR SIZES FOR RISER! |
| | |
| | PLEASE CORRECT PLANS COMPLETELY AND |
| | SUBMIT FOR REVIEW WITH ALL THE |
| | INFORMATION ABOVE ADDRESSED. IF THERE |
| | ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-659-8096 EXT 8372 |