2001-02-05 00:00:00TANK & TUMMY
 1300 N TAMARIND AV
 FL GENERAL CONTRACTORS INC
 PERMIT # 01010048
  
 1)- THE PLANS STUCTURAL NOTES "STANDARD
 BUILDING CODE 1934"
 2)- PAGE 1 OF THIS PLAN DEPICTS AN
 ADDITION FOR A RESIDENCE FROM VARIOUS
 NOTES AND THE PANEL SCHEDULE. CORRECT.
 3)- CANOPY DETAIL; THIS DETAILDEPICTS EI
 THER 1X3 OR 1X4 STRIP SHEATHING,PBC
 AMENDMENTS TO THE SBC1503.1.2.2 REQUIRES
 ALL ROOF COVERINGS SHALL BE APPLIED TO
 SOLID DECKING OR SHEATHING.
 4)- 1503.3.2 AMENDMENTS TO THE SBC ;
 ROOF COVERINGS AND SYSTEMS SHALL BE
 DESIGNED TO WITHSTAND THE APPROPRIATE
 WINDLOADS PRESCRIBED IN SBC 1606. PRO-
 DUCT APPROVAL REPORTS ARE REQUIRED
 SHOWING TESTING FOR 110 MPH WIND LOADS.
 DADE COUNTY OR SBCCI REPORTS ARE ACCEPT-
 ED.
 5)- DISCREPANCY: CANOPY DETAIL GIVES (2)
 METHODS OF ATTACHMENT TO WALL. THE FIRST
 HAS THE FRAMEWORK ATTACHED BY 2 /9"
 TAPCONS, NO SPACING IS GIVEN, THE SHANK
 DIAMETER ISN'T GIVEN. THE SECOND METHOD
 DECRIBES (2) 2X6'S ATTACHED TO THE WALL
 BUT THE SPACING ISN'T GIVEN NOR THE
 HURRICANE STRAPPING FROM THE LEDGER TO
 THE TRUSS.
 6)- DISCREPANCY CANOPY DETAIL VS. FRONT
 ELKEVATION. THE FRONT ELEVATION SHOWS
 23' OF WINDOW & DOOR OPENINGS UNSUPPORT-
 ED PLUS THE ADDITIONAL WEIGHT OF THE
 NEW CANOPY.WHAT TYPE OF MATERIAL IS
 SUPPORTING THIS TYPE OF LOAD? WHERE IN
 RELATIONSHIP DDOES THE ROOF LINE TIE IN?
 7)- SBC 1507.4 SCUPPERS REQUIRED?
 8)- SBC 1606.4.1 / 1707.4.1 GLAZED OPEN-
 INGS REQUIRE PRODUCT TESTING FOR LARGE
 MISSLE IMPACT TESTING. DADE COUNTY OR
 SBCCI REPORT ACCEPTED.
 9)- FL ENERGY CODE CALCULATIONS REQUIRED
 10)- SBC 1203.4.2/ SMC 503.3.2 COMMER-
 CIAL RESTROOMS REQUIRE 2CU.FT/ MIN EX-
 CHANGE OF AIR WHERE THERE IS NO WINDOW.
 11)- FL ACCESSIBILITY CODE 4.1.6 ALTERA-
 TIONS, IF ALTERATIONS OF SINGLE ELEMENTS
 WHEN CONSIDERED TOGETHER, AMOUNT TO AN
 ALTERATION OF A ROOM OR SPACE IN A BUILD
 ING OF FACILITY, THE ENTIRE SPACE SHALL
 BE MADE ACCESSIBLE.
 12)- FL. ACC CODE 4.1.6VERTICAL ACCESS-
 IBILITY, AN ACCESSIBLE ENTRANCE, RAMPS
 NO STEPS.
 13)- FL ACC CODE 4.1.6.2.2 (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA.
 14)- FL ACC CODE (III) AT LEAST ONE
 ACCESSIBLE UNISEX RESTROOM, OUTSING DOOR
 15)- IS THERE A DOOR ON THE WALK IN COOL
 ER?
  