| 2001-02-05 00:00:00 | TANK & TUMMY |
| | 1300 N TAMARIND AV |
| | FL GENERAL CONTRACTORS INC |
| | PERMIT # 01010048 |
| | |
| | 1)- THE PLANS STUCTURAL NOTES "STANDARD |
| | BUILDING CODE 1934" |
| | 2)- PAGE 1 OF THIS PLAN DEPICTS AN |
| | ADDITION FOR A RESIDENCE FROM VARIOUS |
| | NOTES AND THE PANEL SCHEDULE. CORRECT. |
| | 3)- CANOPY DETAIL; THIS DETAILDEPICTS EI |
| | THER 1X3 OR 1X4 STRIP SHEATHING,PBC |
| | AMENDMENTS TO THE SBC1503.1.2.2 REQUIRES |
| | ALL ROOF COVERINGS SHALL BE APPLIED TO |
| | SOLID DECKING OR SHEATHING. |
| | 4)- 1503.3.2 AMENDMENTS TO THE SBC ; |
| | ROOF COVERINGS AND SYSTEMS SHALL BE |
| | DESIGNED TO WITHSTAND THE APPROPRIATE |
| | WINDLOADS PRESCRIBED IN SBC 1606. PRO- |
| | DUCT APPROVAL REPORTS ARE REQUIRED |
| | SHOWING TESTING FOR 110 MPH WIND LOADS. |
| | DADE COUNTY OR SBCCI REPORTS ARE ACCEPT- |
| | ED. |
| | 5)- DISCREPANCY: CANOPY DETAIL GIVES (2) |
| | METHODS OF ATTACHMENT TO WALL. THE FIRST |
| | HAS THE FRAMEWORK ATTACHED BY 2 /9" |
| | TAPCONS, NO SPACING IS GIVEN, THE SHANK |
| | DIAMETER ISN'T GIVEN. THE SECOND METHOD |
| | DECRIBES (2) 2X6'S ATTACHED TO THE WALL |
| | BUT THE SPACING ISN'T GIVEN NOR THE |
| | HURRICANE STRAPPING FROM THE LEDGER TO |
| | THE TRUSS. |
| | 6)- DISCREPANCY CANOPY DETAIL VS. FRONT |
| | ELKEVATION. THE FRONT ELEVATION SHOWS |
| | 23' OF WINDOW & DOOR OPENINGS UNSUPPORT- |
| | ED PLUS THE ADDITIONAL WEIGHT OF THE |
| | NEW CANOPY.WHAT TYPE OF MATERIAL IS |
| | SUPPORTING THIS TYPE OF LOAD? WHERE IN |
| | RELATIONSHIP DDOES THE ROOF LINE TIE IN? |
| | 7)- SBC 1507.4 SCUPPERS REQUIRED? |
| | 8)- SBC 1606.4.1 / 1707.4.1 GLAZED OPEN- |
| | INGS REQUIRE PRODUCT TESTING FOR LARGE |
| | MISSLE IMPACT TESTING. DADE COUNTY OR |
| | SBCCI REPORT ACCEPTED. |
| | 9)- FL ENERGY CODE CALCULATIONS REQUIRED |
| | 10)- SBC 1203.4.2/ SMC 503.3.2 COMMER- |
| | CIAL RESTROOMS REQUIRE 2CU.FT/ MIN EX- |
| | CHANGE OF AIR WHERE THERE IS NO WINDOW. |
| | 11)- FL ACCESSIBILITY CODE 4.1.6 ALTERA- |
| | TIONS, IF ALTERATIONS OF SINGLE ELEMENTS |
| | WHEN CONSIDERED TOGETHER, AMOUNT TO AN |
| | ALTERATION OF A ROOM OR SPACE IN A BUILD |
| | ING OF FACILITY, THE ENTIRE SPACE SHALL |
| | BE MADE ACCESSIBLE. |
| | 12)- FL. ACC CODE 4.1.6VERTICAL ACCESS- |
| | IBILITY, AN ACCESSIBLE ENTRANCE, RAMPS |
| | NO STEPS. |
| | 13)- FL ACC CODE 4.1.6.2.2 (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA. |
| | 14)- FL ACC CODE (III) AT LEAST ONE |
| | ACCESSIBLE UNISEX RESTROOM, OUTSING DOOR |
| | 15)- IS THERE A DOOR ON THE WALK IN COOL |
| | ER? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |