| Plan Review Notes For Permit 01010035 |
| Permit Number |
01010035 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-11 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE, NOW THAT A RISER | | | DIAGRAM IS SUBMITTED SHOWING WHERE | | | POWER IS COMING FROM. PLEASE NOTE THAT A | | | LOAD CALCULATION OF EXISTING SERVICE | | | ISNEEDED. PER 220-3-C-1 | | | | | | 2)NOTE: FROM FIRTS NOTES, PLEASE SHOW | | | GROUNDING AT DETACHED STRUCTURE. MUST | | | HAVE GROUND RODE AND COLD WATER BOND, | | | PER ART250 | | | | | | 3)NOTE: PLEASE NOTE FROM FIRST REVIEW | | | NOTES, BATH CIRCUIT PER 210-11-C-3. | | | PLAN SHOWS FEEDING OUTSIDE OUTLET? | | | SHARING | | | CIRCUIT WITH BATH OUTLET IS NOT | | | PERMITTED. | | | | | | 4)NOTE: PLEASE CLARIFY LOAD FOR WATER | | | HEATER? PLAN SHOWS 8/2 FEED.SUBMIT | | | SIZE OF WATER HEATER. | | | | | | 5)NOTE: PLEASE NOTE A MEANS OF EGRESS | | | LIGHTING IS REQ`D AT DOOR. PER 210-70. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION, IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|