Plan Review Notes
Plan Review Notes For Permit 01010035
Permit Number 01010035
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-11 00:00:00************** UNSAT ****************
  
 1)NOTE: PER NEC ART 225-31. A MEANS OF
 DISCONNECT AND PANEL IS REQ`D AT THE
 DETACHED STRUCTURE.PLEASE SUBMIT RISER
 DIAGRAM SHOWING THIS. PLEASE SUBMIT
 PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE NOTE PER 210-11-C-3 ALL
 REQ`MENTS ARE TO BE MET. MUST BE 20AMP
 AND #12. DEDICATED CIRCUIT(S).
  
 3)NOTE: PLEASE SHOW GROUNDING AT
 DETACHED STRUCUTRE PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATIONFOR
 REVIEW, IF THERE ARE ANY QUESTIONS, PLE
 SE CALL;
  
 DEWEY PLLMER
 ELECTRCIAL PLAN REVIEW
 659-8096