| Plan Review Notes For Permit 01010035 |
| Permit Number |
01010035 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-22 00:00:00 | CHECKLIST: | | | | | | 1-PROVIDE CONNECTION DETAILS. SPECIFY | | | CONNECTORS TOP AND BOTTOM. SPECIFY | | | ROOF CONNECTORS. | | | 2-PROVIDE PRODUCT APPROVALS FOR: | | | -EXTERIOR DOORS AND WINDOWS. | | | -FLAT ROOF SYSTEM. | | | -STORM SHUTTERS FOR GLAZED OPENINGS. | | | 3-NEED TO RECORD A NOTICE OF | | | COMMENCEMENT(NOC). | | | 4-SEE COMMENTS BY ELECTRICAL PLAN | | | REVIEWER. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT JULIO GOMEZ AT 659-8096 EXT. | | | 8232. |
|