| Plan Review Notes For Permit 01010021 |
| Permit Number |
01010021 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-07 00:00:00 | THE SAME THREE COMMENTS AS THE FIRST | | | REVIEW: | | | 1)- SHEET A1 MAKES REFRENCE TO THE | | | SOUTH FL BUILDING CODE IN SEVERAL PLACES | | | THE CITY USES THE 1997 STANDARD BUILDING | | | CODE. PLEASE REVISE AS NECESSARY. | | | 2)- THE PLANS DONOT CLEARLY NOTE THE | | | REQUIRED USE OF FIRE RETARDANT TREATED | | | WOOD BLOCKING IN PARTITIONS. SEE SBC | | | 609.1.2. SEE SHEETS A-9. | | | 3)- SHOW THE METHOD OF FIRE PROTECTION | | | FOR THE NEW STEEL BEAMS, (2HR), AS | | | REQUIREDBY SBC TABLE 600 FOR TYPE II | | | CONSTRUCTION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|