| Plan Review Notes For Permit 01010021 |
| Permit Number |
01010021 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-11 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS. | | | 3) ADDITIONAL EMERGENCY LIGHTING APPEARS | | | TO BE NEEDED IN CORRIDORS OF SPACE. | | | 4) THE FIRE ALARM NOTES SECTION | | | INDICATES CLASS B, STYLE C CIRCUITS. | | | ONLY CLASS A, STYLE D CIRCUITS ALLOWED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|