| Plan Review Notes For Permit 01010021 |
| Permit Number |
01010021 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-17 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRNET PER 110-9. | | | PLEASE NOTE AIC RATING FOR MAIN? | | | PLEASE PROVIDE CLARIFICATION ON MAIN | | | DISCONNECT. 200/220A. 220A? IS NOT A | | | STANDARD SIZE UNDER 240-6. TYPE O | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | | E CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|