2001-01-10 00:00:001 SHEET A1 MAKES REFERENCE TO THE SOUTH
 FL BUILDING CODE IN SEVERAL PLACES.THE
 CITY USES THE 1997 STANDARD BUILDING
 CODE.PLEASE REVISE AS NECESSARY.
  
 2THE PLANS DO NOT CLEARLY NOTE THE
 REQUIRED USE OF FIRE RETARDANT TREATED
 WOOD BL0CKING IN PARTITIONS.SEE SBC
 609.2.
  
 3SHOW THE METHOD OF FIRE PROTECTION
 FOR THE NEW STEEL BEAMS, (2HR), AS
 REQUIRED BY SBC TABLE 600 FOR TYPE II
 CONSTRUCTION.
  