| Plan Review Notes For Permit 01010021 |
| Permit Number |
01010021 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-10 00:00:00 | 1 SHEET A1 MAKES REFERENCE TO THE SOUTH | | | FL BUILDING CODE IN SEVERAL PLACES.THE | | | CITY USES THE 1997 STANDARD BUILDING | | | CODE.PLEASE REVISE AS NECESSARY. | | | | | | 2THE PLANS DO NOT CLEARLY NOTE THE | | | REQUIRED USE OF FIRE RETARDANT TREATED | | | WOOD BL0CKING IN PARTITIONS.SEE SBC | | | 609.2. | | | | | | 3SHOW THE METHOD OF FIRE PROTECTION | | | FOR THE NEW STEEL BEAMS, (2HR), AS | | | REQUIRED BY SBC TABLE 600 FOR TYPE II | | | CONSTRUCTION. | | | | | | HAROLD PISKURA |
|