| Plan Review Notes For Permit 01010004 |
| Permit Number |
01010004 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-29 00:00:00 | ****************DENIED****************** | | | 1. INSUFFICIENT INFORMATION TO PROVIDE | | | COMPLETE REVIEW. | | | 2. PLEASE CLARIFY MECH PLAN NOTES , I.E. | | | UNABLE TO LOCATE NOTES E,H, I, J, K, L, | | | AND M. UNABLE TO TELL IF O OR Q IS | | | SHOWN, UNABLE TO LOCATE THE OTHER | | | LETTER. | | | 3. ELECTRICAL PLAN SHOWS 10 DUCT SMOKE | | | DETECTORS. MECH SHOWS 7 RTU'S. SEVERAL | | | DUCT SMOKE DETECTORS APPEAR ON CHASE | | | WALLS,PROVIDE INFORMATION ON WHAT UNITS | | | THESE SERVE. | | | 4. NOTE 14 INDICATES AUX. PAN FOR AHU'S, | | | WHERE ARE THESE AHU'S ? | | | 5. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2. NOTE THAT | | | IF EXHAUST FANS ARE SWITCHED W/ BATHROOM | | | LIGHTS THEY CAN'T BE USED FOR AIR | | | BALANCE. | | | 6. PROVIDE INFORMATION ON EMERGENCY | | | GENERATOR REQARDING LOCATION OF | | | EQUIPMENT AND EXHAUST LOCATION AND | | | TERMINATION. |
|