2001-01-09 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 2) PLEASE SUBMIT FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILING OF TENANT SPACE.
 4) PLEASE PROVIDE MORE ADDITIONAL
 INFORMATION ON NOTE 120, SHEET A-3,
 "WATER CURTAIN".
  