| 2001-01-17 00:00:00 | ******************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | |
| | 2)NOTE: PLEASESHOW ALL NEW BRANCH |
| | CIRCUIT #`S ON PLANS AND CORRELATE WITH |
| | PANEL SCHEDULES. SHOW PANEL SCHEDULES. |
| | |
| | 3)NOTE: PLEASE PROVIDE CLARIFICATION ON |
| | ATS.GENERATOR/ BLDG MAIN(S) LOCATIONS. |
| | PLEASE PROVIDE CLARIFICATION OF GROUPING |
| | OF MAINS. PER 230-72/23-72 |
| | |
| | 4)NOTE: PLEASE NOTE, DEPENDING ON |
| | LOCATION OF THE ABOVE IN NOTE 3. A |
| | INLINE DISCONNECT MAY BE REQ`D FROM |
| | GENERATOR TO ATS. |
| | |
| | 5)NOTE: PLEASE SEE 230-76 AND 230-79 FOR |
| | #12 NOTE ON E-5. SHUNT TRIP SHOWN? |
| | THISIS NOT AN ACCEPTABLE MEANS OF |
| | DISCONNECTPER THE ABOVE ARTS. |
| | |
| | 6)NOTE: PLEASE NOTE, THAT I HAVE SEEN |
| | THE NOTE ON THE TOP OF E-5 PERTAINING |
| | TO-CIRCUITPANELS/ AND CALCULATIONS. |
| | THE FOLLOWING MUST BE SUBMITTED. ALL NEW |
| | EQUIPMENT MUST HAVE PANEL SCHEDULES |
| | SHOWN. I WILL ACCEPT EXISTING |
| | PANELS/CIRCUIT TO BE REVISED. ALL NEW |
| | MUST BE SHOWN. PLEASE ALSO NOTE THAT |
| | THE LOAD CALCULATIONS ARE REQ`D AT THE |
| | PRESENT TIME. PLEASE MAKE SURE ALL |
| | CONTINUOUS LOADS ARE SHOWN AT 125%. |
| | |
| | 7)NOTE: PLEASE SHOW THE GFI OUTLET REQ`D |
| | FOR A/C EQUYIPMENT PER 210-63 OF NEC |
| | AND 309.1 OF MECH CODE. |
| | |
| | 8)NOTE: PLEASE SEE E-5 #46 NOTE SAYS |
| | NEMA 3R DISCONNECT. SIZE? VOLTAGE? ETC. |
| | PLEASE PROVIDE MORE INFORMATION ON #43 |
| | NOTE. |
| | |
| | 9)NOTE: PLEASE SEE E-1 PLEASE SHOW PANEL |
| | C-1. ALSO POWER CONDITIONER LOCATION. |
| | |
| | 10)NOTE:PLEASE SHOW GROUNDING FOR |
| | GENERATOR PER 250 OF NEC. |
| | |
| | 11)NOTE: PLEASE LIST VOLTAGES OF ALL |
| | NEWAND EXISTING EQUIPMENT. IF ANY OF |
| | THESE ARE 277/480V PLANS ARE TO SIGNED |
| | AND SEALED BY A PE. UNDER SEC 553-79 6A |
| | OF THE F.A.C. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |