| Plan Review Notes For Permit 00121288 |
| Permit Number |
00121288 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE | | | LOCATED NO FARTHER THAN 150 FEET FROM | | | A FIRE HYDRANT. | | | 2) A SPARE HEAD BOX CONTAINING AT LEAST | | | 12 SPARE SPRINKLER HEADS AND WRENCH | | | ARE TO BE PROVIDED. | | | 3) FIRE SPRINKLER SYSTEM TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|