| Plan Review Notes For Permit 00121285 |
| Permit Number |
00121285 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. ALL | | | PANELS/MAINS/BRKRS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE SUBMIT MORE DETAIL ON THE | | | PANEL SCHEDULES SHOWING WIRE SIZES AND | | | BRKR SIZES TO CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|