Plan Review Notes
Plan Review Notes For Permit 00121285
Permit Number 00121285
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED. ALL
 PANELS/MAINS/BRKRS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE SUBMIT MORE DETAIL ON THE
 PANEL SCHEDULES SHOWING WIRE SIZES AND
 BRKR SIZES TO CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372