Plan Review Notes
Plan Review Notes For Permit 00121282
Permit Number 00121282
Review Stop B
Sequence Number 2
Notes
Date Text
2001-02-15 00:00:00SECOND CHECKLIST:
 1-IMPACT FEES ARE STILL NOT PAID. PAY
 IMPACT FEES TO PALM BEACH COUNTY, GET
 DRAWINGS STAMPED AND BRING RECEIPT.
 2-STORM PANELS INFORMATION IS STILL
 INCOMPLETE:
 -NEED KEY PLAN THAT MATCHES MODEL.
 -STORM PANEL DWG # 01-246 CAN'T BE USED
 AS A REFERENCE BECAUSE IT IS NOT PART
 OF THE DRAWINGS APPROVED IN THE SBCCI
 EVALUATION REPORT.
 -SEE LIMITATIONS ON SHEET 3 OF 3 OF
 SBCCI REPORT REGARDING THE USE OF TRU-
 FAST TAP GRIP ANCHORS. CHECK THE MIN.
 COMPRESSIVE STRENGTH OF CONCRETE
 MASONRY UNITS.
 -CLEARLY INDICATE ON ANCHOR SCHEDULE
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AN SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,
 MIN. EDGE DISTANCE, MAX. PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (NOTE: THIS IS CONCRETE
 BLOCK CONSTRUCTION, NOT CONCRETE).
 -THIS COMPLETE INFORMATION MAY BE
 SUBMITTED UNDER A SEPARATE PERMIT.
 3-ROOF FRAMING PLAN:
 -SPECIFY CONNECTORS THAT WILL RESIST
 THE LOADS AS CALCULATED ON THE
 ENGINEERED TRUSSES. EG: SEE TRUSSES
 MG2 AND HG1.
 4-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVAL FOR:
 -GARAGE SIDE DOOR AND OTHER FRENCH
 DOORS. SEE SIZES SPECIFIED ON PLANS.
 -WINDOW MULLIONS, SINGLE HUNG WINDOWS,
 ARCHED WINDOWS & SLIDING GLASS DOORS.
 PRODUCT APPROVAL FROM NORANDEX IS NOT
 ACCEPTABLE UNLESS IT IS SIGNED, SEALED
 AND DATED BY THE ENGINEER OF RECORD
 FOR THIS SPECIFIC LOCATION.
 5-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7 AND TABLE 1804.2.7.3 OF CITY
 AMENDMENTS TO SBC 1997.
 NOTE: THIS REPORT WAS NEVER SUBMITTED
 TO THE CITY.
 -ALSO, DENSITY TESTS SUBMITTED HAVE THE
 WRONG LOT AND THE NAME OF THE BUILDER
 IS DIFFERENT. WHY?.
  
  
  
  
  
 JULIO GOMEZ, BUILDING PLAN REVIEWER,
 659-8096 EXT. 8232.