| 2001-02-15 00:00:00 | SECOND CHECKLIST: |
| | 1-IMPACT FEES ARE STILL NOT PAID. PAY |
| | IMPACT FEES TO PALM BEACH COUNTY, GET |
| | DRAWINGS STAMPED AND BRING RECEIPT. |
| | 2-STORM PANELS INFORMATION IS STILL |
| | INCOMPLETE: |
| | -NEED KEY PLAN THAT MATCHES MODEL. |
| | -STORM PANEL DWG # 01-246 CAN'T BE USED |
| | AS A REFERENCE BECAUSE IT IS NOT PART |
| | OF THE DRAWINGS APPROVED IN THE SBCCI |
| | EVALUATION REPORT. |
| | -SEE LIMITATIONS ON SHEET 3 OF 3 OF |
| | SBCCI REPORT REGARDING THE USE OF TRU- |
| | FAST TAP GRIP ANCHORS. CHECK THE MIN. |
| | COMPRESSIVE STRENGTH OF CONCRETE |
| | MASONRY UNITS. |
| | -CLEARLY INDICATE ON ANCHOR SCHEDULE |
| | THE SPECIFIC MOUNTING CONDITIONS AND |
| | ANCHOR TYPE AN SPACING TO BE USED |
| | ACCORDING TO THE DESIGN PRESSURES, |
| | MIN. EDGE DISTANCE, MAX. PANEL SPAN, |
| | CONNECTION TYPE AND STRUCTURE TO BE |
| | ATTACHED TO (NOTE: THIS IS CONCRETE |
| | BLOCK CONSTRUCTION, NOT CONCRETE). |
| | -THIS COMPLETE INFORMATION MAY BE |
| | SUBMITTED UNDER A SEPARATE PERMIT. |
| | 3-ROOF FRAMING PLAN: |
| | -SPECIFY CONNECTORS THAT WILL RESIST |
| | THE LOADS AS CALCULATED ON THE |
| | ENGINEERED TRUSSES. EG: SEE TRUSSES |
| | MG2 AND HG1. |
| | 4-PROVIDE CURRENT SBCCI OR DADE COUNTY |
| | PRODUCT APPROVAL FOR: |
| | -GARAGE SIDE DOOR AND OTHER FRENCH |
| | DOORS. SEE SIZES SPECIFIED ON PLANS. |
| | -WINDOW MULLIONS, SINGLE HUNG WINDOWS, |
| | ARCHED WINDOWS & SLIDING GLASS DOORS. |
| | PRODUCT APPROVAL FROM NORANDEX IS NOT |
| | ACCEPTABLE UNLESS IT IS SIGNED, SEALED |
| | AND DATED BY THE ENGINEER OF RECORD |
| | FOR THIS SPECIFIC LOCATION. |
| | 5-PROVIDE SOIL TEST REPORT AS PER SEC. |
| | 1804.2.7 AND TABLE 1804.2.7.3 OF CITY |
| | AMENDMENTS TO SBC 1997. |
| | NOTE: THIS REPORT WAS NEVER SUBMITTED |
| | TO THE CITY. |
| | -ALSO, DENSITY TESTS SUBMITTED HAVE THE |
| | WRONG LOT AND THE NAME OF THE BUILDER |
| | IS DIFFERENT. WHY?. |
| | |
| | |
| | |
| | |
| | |
| | JULIO GOMEZ, BUILDING PLAN REVIEWER, |
| | 659-8096 EXT. 8232. |