| Plan Review Notes For Permit 00121280 |
| Permit Number |
00121280 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS WHEN INSTALLED ARE TO | | | BE A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 2) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | | IS TO BE AUDIBLE THROUGHOUT THE | | | BUILDING. | | | 3) THE PERFORMANCE HALL PORTION OF THE | | | FIRE ALARM SYSTEM IS TO BE TESTED WITH | | | FIRE RESCUE PERSONNEL. | | | 4) HOOD SUPPRESSION SYSTEMS TO BE | | | CONNECTED TO BUILDINGS FIRE ALARM | | | SYSTEM. | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|