| Date |
Text |
| 2001-01-23 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING STAMPED DRAWINGS AND RECEIPT. |
| | 2-REVISE ENERGY CALCULATIONS: |
| | -THERE ARE 4 BEDRMS, NOT 3. SEE PLANS. |
| | -REVISE A/C AREA AND CEILING AREA AS |
| | REQUIRED TO MATCH PLANS. |
| | -PROVIDE ORIGINAL SIGNATURES. |
| | 3-STORM PANELS: |
| | -PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE (SEE CITY SAMPLE). |
| | -SPECIFY/HIGHLIGHT/CIRCLE SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TO BE |
| | USED ACCORDING TO MEAN ROOF HEIGHT, |
| | DESIGN PRESSURES, PANEL SPAN, EDGE |
| | DISTANCE, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO. |
| | -DRAWINGS AND PRODUCT APPROVAL REPORT |
| | DON'T MATCH. |
| | 4-INTERIOR BEARING PARTITION FOOTING TO |
| | HAVE 16" MIN. DEPTH AS PER SECTION |
| | 1804.1.3 SBC 1997 AND SECTION |
| | 1804.1.9 CITY AMENDMENTS TO SBC 1997. |
| | 5-SEE COMMENTS ON PLANS. INCLUDING THOSE |
| | BY THE OTHER TRADES.AND REVISE/UPDATE. |
| | 6-REAR ELEVATION AND FLOOR PLAN DON'T |
| | MATCH. SEE COLUMN BET. FRENCH DOORS. |
| | 7-TRUSS DRAWINGS: |
| | -ENGINEERED TRUSSES TO HAVE ORIGINAL |
| | SIGNATURE, DATE AND SEAL. FL. STATUTES |
| | -UPDATE GENERAL DETAILS AND SIGN, SEAL |
| | AND DATE ACCORDINGLY. 471 FL. STATUTES |
| | -TRUSS LAYOUT TO HAVE ENGINEER'S |
| | SEAL, DATE AND SIGNATURE ALONG WITH |
| | INFORMATION AS REQUIRED BY CHAPTER 471 |
| | OF FLORIDA STATUTES. |
| | -CLEARLY INDICATE ON ENGINEERED TRUSSES |
| | AND TRUSS LAYOUT WHO REVIEWED THEM. |
| | -REVISE ROOF CONNECTOR SCHEDULE SHOWING |
| | CONNECTORS THAT WILL RESIST THE UPLIFT |
| | LOADS CALCULATED IN THE ENGINEERED |
| | TRUSSES. SEE COMMENTS ON SHEET 3B. |
| | 8-PROVIDE COMPLETE SPECIFICATIONS FOR |
| | INTERIOR BEARING WALL: STUD SPACING |
| | AND MAXIMUM UNSUPPORTED STUD HEIGHT. |
| | DETAIL ON SHEET 3B LACKS THIS INFO. |
| | 9-PROVIDE CURRENT SBCCI OR DADE COUNTY |
| | PRODUCT APPROVALS FOR: |
| | -ENTRY DOOR WITH SIDELITE ASSEMBLY |
| | (WITH LEGIBLE DRAWINGS). |
| | -GARAGE SIDE DOOR. |
| | -WINDOW MULLIONS. |
| | -FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY |
| | (OR AS SHOWN ON REAR ELEVATION). |
| | -SINGLE HUNG WINDOWS. |
| | -RECTANGULAR AND ROUND FIXED WINDOWS. |
| | 10-PROVIDE SOIL TEST REPORT AS PER SECT. |
| | 1804.2.7 AND TABLE 1804.2.7.3 OF CITY |
| | AMENDMENTS. (NOT SOUTH FLORIDA BLDG |
| | CODE -BROWARD EDITION). |
| | 11-SOIL TEST REPORT AS PER SEC 1804.2.7 |
| | AND TABLE 1804.2.7.3 CITY AMENDMENTS. |
| | NOT SFBC (BROWARD ED.). |
| | NOTES: |
| | -PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO THE ORIGINALS |
| | IN ORDER TO EXPEDITE THE REVIEW PROCESS |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |