| Plan Review Notes For Permit 00121189 |
| Permit Number |
00121189 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION TO BE NO | | | FARTHER THAN 150 FEET FROM A FIRE | | | HYDRANT. | | | 2) THE ENTIRE BUILDING IS TO BE | | | COMPLETELY FIRE SPRINKLER PROTECTED. | | | THIS INCLUDES ALL ELECTRICAL, MECHANICAL | | | AND SERVICE ROOMS. ALL VERTICAL SHAFTS | | | ARE ALSO TO BE PROPERLY FIRE SPRINKLER | | | PROTECTED. | | | 3) THE STANDPIPE SYSTEM IS REQUIRED TO | | | PROVIDE 750 GPM AT 65 PSI AT THE ROOF. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|