| 2001-01-08 00:00:00 | ***************** UNSAT **************** |
| | |
| | 1)NOTE: PLANS SHOW A MAIN DISCONNECT |
| | NEXT TO METERCAN AND RISER SHOWS NO MAIN |
| | DSIC??? PLEASECORRELATE |
| | |
| | 2)NOTE: PLEASE NOTE THAT RISER SHOWS 3#1 |
| | CONDUCTORS IN A 8" CONDUIT? PLEASE CORR- |
| | -ECT OR CLARIFY. |
| | |
| | 3)NOTE: PLANS SHOW A FAN BEING SWITCHED |
| | IN BEDROOMS AND NO LIGHT? IS IT A FAN/ |
| | LIGHT? IF SO PLEASE SHOW FANS W/ LT KITS |
| | |
| | 4)NOTE: PLEASE NOTE THAT PLANS DO NOT |
| | SHOW THE DISC REQ`D FOR A/C CU. PLEASE |
| | SHOW PER 440-11 |
| | |
| | 5)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | CU PER MECH CODE 309.1 AND/OR GFI OUTLET |
| | MISSING IN REAR OF DWELLING PER 210-52E |
| | THAT MAY SERVE AS GFI FOR CU. |
| | |
| | 6)NOTE: PLEASE SHOW OUTLET INFRONT OF |
| | DWELLING AS GFI PER 210-8 |
| | |
| | 7)NOTE: PLEASE KW FOR ALL ON PANEL SCHED |
| | -ULE AND SHOW LOAD CACULATIONS PER 215-5 |
| | |
| | 8)NOTE: PLEASE SHOW THE REQ`D DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210-11-C-3 |
| | MUST BE #12 AND 20A |
| | |
| | 9)NOTE: PLEASE NOTE MISSING OUTLETS PER |
| | 210-52, 2` OF WALL SPACE. |
| | |
| | 10)NOTE: PLEASE NOTE THAT LOCATION OF |
| | SD IN COMMON AREA IS SHOWN TOO CLOSE TO |
| | KITCHEN. PLEASE CHECK NFPA FOR SD SPAC- |
| | -ING REQ`MENTS |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 659-8096 EXT 8372 |