| Plan Review Notes For Permit 00121123 |
| Permit Number |
00121123 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.LIST CFM'S FOR EACH DROP. | | | | | | 2.R/A CANNOT BE RESTRICTED TO ONE ROOM. | | | IS A/H IN GARAGE? IF SO DROPS AND R/A | | | CANNOT BE LOCATED THERE. | | | | | | 3.CAN 12" DUCT CARRY ENOUGH CFM'S TO | | | SUPPLY 5 DROPS? | | | | | | A/C PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8377 |
|