Plan Review Notes
Plan Review Notes For Permit 00121116
Permit Number 00121116
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-13 00:00:00DENIED;
 1.HANDICAP LAV. CLEARANCE FROM FLOOR TO
 BOTTOM OF LAV.IS 29" PER. 97 FACBC
 FIG. 31 PAGE 109.
 2.SINK SHALL BE MOUNTED WITH COUNTER NO
 HIGHER THAN 34" FACBC 4.24.2 ALSO
 COMPLY WITH 4.24.4 AND 4.24.6.
 3.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC SECS. 4.1.3 (10) AND 4.15.
 PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING OR STOOPING.
  