2001-01-09 00:00:00BUILDING PLAN REVIEW
 1). THE DRINKING FOUNTAIN IN THE VESTI-
 BULE BLOCKS THE EGRESS OF THE RESTROOMS,
 A REQUIRED 3'-0" IS THE MINIMUM ALLOWED
 SEE SECTIONS SBC 1003.3.4/ 1003.2.3.
 2). THE PLANS CALL FOR THE TENANT SPACE
 TO BE FIRE SPRINKLERED, SUBMIT PLANS &
 CALCULATIONS FOR THE FIRE SPRINKLERS.
 3). SBC 803.2 INTERIOR FINISH MATERIALS
 OTHER THANTHOSE APPLIED TO FLOORS
 SHALL BE CLASSIFIED IN ACCORDANCE WITH
 ASTM E 84. PLEASE SUBMIT A LIST OF FIN-I
 SHES.
 4). SBC 1606.4.1- IMPACT GLAZING FROM
 WINDBORN DEBRIS THE STOREFRONT GLAZING &
 DOOR UNIT WILL REQUIRE PRODUCT TESTING,
 2 DADE COUNTY OR SBCCI REPORTSWILL BE
 REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412