Review Stop M
Sequence Number 2
Notes
Date Text
2001-03-19 00:00:00NOTE:MUST COMPLY WITH 1997 SMC SECTION
 406FOR FAN SHUTDOWN BY DUCT
 SMOKE DETECTOR AND NOTIFICATION
 TO HORN/STROBE ALARM AS PER NFPA
 90A, 4-4.4.1 THRU 4-4.4.3.
  
 FILED WITH MASTER # 00051379.