2001-02-12 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PAGE 4 OF 7
 IS NOT SIGNED AND SEALED BY THE
 ENGINEEROF RECORD. PLANS ARE TO SIGNED
 AND SEALED PER 471.025, 61G-15-23.00.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 NO OTHER CIRCUITS ARE PERMITTED TO BE
 ONWITH KITCHEN CIRCUITS. PLEASE NOTE
 THEREQ`MENTS FOR BATHS ARE LISTED IN
 THE NEC UNDER 210-52D AND 210-11-C-3.
  
 3)NOTE : PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR SHOWN AS #5 IS NOT
 A SIZE LISTED UNDER "AWG" AND NEC 250-66
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  