| Plan Review Notes For Permit 00120947 |
| Permit Number |
00120947 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE : PLEASE SUBMIT AIC RATINGS FOR | | | NEW EQUIPMENT BEING INSTALLED. MAINS/PAN | | | -ELS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURENT PER 110-9 | | | | | | 2)NOTE: PLEASE NOTE PER 250-50 BLDG. | | | STEEL IS TO BE PART OF THE GROUNDING | | | ELECTRODE SYSTEM. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D DEDICATED | | | BATH CIRCUIT PER 210-11-C-3 #12/20A | | | | | | 4)NOTE: PLEASE SHOW SOME MORE DETAIL | | | ON CONDUCTORS AND CONDUIT FROM METER TO | | | MAIN AND PANEL. A NOTE IS SHOWN ON LEFT | | | THAT SHOWS AS 3-3/0`S AND 1 1/2" RIGID. | | | PLEASE SHOW EQUIPMNET GROUND FROM MAIN | | | TO PANEL IF NOT RIGID. | | | | | | 5)NOTE: PLEASE NOTE ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE INCLUDING ISLAND | | | ARE TO BE SHOWN AS GFI/GFI PROTECTED | | | PER 210-8-A-6 | | | | | | 6)NOTE: PLEASE NOTE PER NFPA-72 2-2.1.1. | | | .1. SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS ALSO | | | EXISTING BEDROOMS WILL NEED SMOKE DETECT | | | -TORS FOR MORE THAN 50% OF NEW DWELLING | | | INSIDE AND OUTSIDE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|