Plan Review Notes
Plan Review Notes For Permit 00120947
Permit Number 00120947
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE : PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED. MAINS/PAN
 -ELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURENT PER 110-9
  
 2)NOTE: PLEASE NOTE PER 250-50 BLDG.
 STEEL IS TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT PER 210-11-C-3 #12/20A
  
 4)NOTE: PLEASE SHOW SOME MORE DETAIL
 ON CONDUCTORS AND CONDUIT FROM METER TO
 MAIN AND PANEL. A NOTE IS SHOWN ON LEFT
 THAT SHOWS AS 3-3/0`S AND 1 1/2" RIGID.
 PLEASE SHOW EQUIPMNET GROUND FROM MAIN
 TO PANEL IF NOT RIGID.
  
 5)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE INCLUDING ISLAND
 ARE TO BE SHOWN AS GFI/GFI PROTECTED
 PER 210-8-A-6
  
 6)NOTE: PLEASE NOTE PER NFPA-72 2-2.1.1.
 .1. SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS ALSO
 EXISTING BEDROOMS WILL NEED SMOKE DETECT
 -TORS FOR MORE THAN 50% OF NEW DWELLING
 INSIDE AND OUTSIDE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372